Fire smoke exhaust fans are the core equipment of building fire protection systems, responsible for expelling toxic smoke and buying time for personnel evacuation during fire incidents. According to the "Code for Fire Protection Design of Buildings" GB50016 and "Technical Standard for Smoke Management and Exhaust Systems in Buildings" GB51251-2015, exhaust facilities must be installed in underground rooms exceeding 100㎡ and evacuation corridors exceeding 20m in length.
Xinfeng fire smoke fans are all certified by the Ministry of Public Security Fire Products Quality Certification Center (CCCF), complying with GB51251-2015 and GB12361-2013 standards.
| Clause | Requirement | Xinfeng Configuration |
|---|---|---|
| 4.7.2 | Exhaust fan must operate continuously at 280°C for 30min | Fireproof materials + high-temperature bearings |
| 4.7.5 | Fan room fire resistance grade ≥2.0h | Fireproof partition walls + fire doors |
| 5.2.2 | Exhaust volume calculated by air change rate | Precise air volume calculation |
| 5.2.8 | System worst-loop volume ≤10% | CFD simulation optimization |
| 6.3.1 | 280°C fire smoke exhaust damper at fan outlet | Standard eutectic alloy valve |
| Parameter | Specification |
|---|---|
| Certification | CCCF certified, certificate number verifiable |
| Temperature | 280°C continuous operation 30min, no deformation |
| Air Volume | 5,000-50,000 m³/h |
| Material | Carbon steel/304 stainless steel |
| Parameter | Specification |
|---|---|
| Temperature Resistance | 500°C, continuous operation 1h |
| Industry | Metallurgy/glass industry specialized |
| Design | Special fireproof materials + water-cooled bearings |
| Parameter | Specification |
|---|---|
| Explosion-Proof | Ex d IIB T4 Gb explosion-proof certification |
| Environment | Chemical plants/gas stations specialized |
| Feature | Meets both fire and explosion-proof requirements |
| Type | Installation Position | Air Volume Range | Xinfeng Model |
|---|---|---|---|
| Roof Fire Smoke Exhaust Fan | Roof | 5,000-50,000 m³/h | XFJ-FR-T |
| Ceiling Fire Smoke Exhaust Fan | Inside ceiling | 3,000-30,000 m³/h | XFJ-FR-D |
| Vertical Fire Smoke Exhaust Fan | Machine room | 10,000-100,000 m³/h | XFJ-FR-V |
| Duct Fire Smoke Exhaust Fan | In duct | 2,000-20,000 m³/h | XFJ-FR-P |
| Parameter | Description | Xinfeng Configuration |
|---|---|---|
| Exhaust Volume | Calculated by GB51251 formula | Space volume × air change rate |
| Exhaust Temperature | 280°C (flue gas temperature) | Fireproof design |
| Total Pressure | ≥500Pa (considering pipeline resistance) | Multi-impeller series |
| Motor Power | 1.2x safety factor | 2.2-75kW |
| Advantage | Description |
|---|---|
| Full Product Line CCCF Certification | Certificates complete |
| Complete Fire Resistance Test Reports | Can respond to fire inspection |
| System Design Solutions | Ensure smoke exhaust effectiveness |
| 24-Hour Emergency Service | Fire equipment allows no compromise |
| 2-Year Warranty | Lifetime maintenance |
Q: Does the fire fan require regular testing?
A: Yes. Monthly manual start test, quarterly automatic start test, annual comprehensive inspection. Xinfeng provides annual maintenance services.
Q: What is the difference between fire smoke exhaust fan and supply fan?
A: Fire smoke exhaust fan expels smoke, supply fan sends positive pressure to evacuation passages. They work together to form a complete smoke management system.
Q: How long is the fire fan certification valid?
A: CCCF certification valid for 5 years, requires renewal. Xinfeng certificates remain valid and can be verified at any time.
Q: What is the delivery time for Xinfeng fire fans?
A: Standard models 10-15 days, custom models 20-30 days. Fire equipment urgent orders prioritized.
Guangdong Xinfeng Fan Co., Ltd.
| Item | Information |
|---|---|
| Phone | 400-XXX-XXXX |
| sales@gzxffj.com | |
| Website | www.gzxffj.com |
🔥 Fire equipment allows no compromise!